一、Scope of application
AC gapless metal oxide arresters are used to protect the insulation of AC power transmission and transformation equipment from lightning overvoltage and operating overvoltage damage. It is suitable for over-voltage protection of transformers, power transmission lines, power distribution panels, switch cabinets, power metering boxes, vacuum switches, parallel compensation capacitors, rotating electrical machines and semiconductor devices.
二、Features and principles
The AC gapless metal oxide arrester has excellent nonlinear volt-ampere characteristics, good response characteristics, no freewheeling, large current capacity, low residual voltage, strong suppression of overvoltage, pollution resistance, anti-aging, and no altitude constraints. Simple structure, no gaps, tight sealing, long life and other characteristics
The lightning arrester presents a high resistance state under normal system working voltage, and only microampere current passes through. Under the action of overvoltage and high current, it presents low resistance, thus limiting the residual voltage at both ends of the arrester.
三、Electrical characteristics
The characteristic parameters of AC gapless metal oxide arresters are shown in the table below.
四、Use and maintenance
1. Selection: The use of lightning arresters should be based on the requirements of the place of use in accordance with this manual
The electrical parameters in the table should be selected reasonably with reference to the "Guidelines for the Use of AC Gapless Metal Oxide Surge Arresters".
2. Acceptance: Each box of arrester is accompanied by a certificate and a manual. The appearance should be checked during acceptance to prevent sharp blades from scratching the jacket. Do not remove the upper and lower end covers. When accepting, it should be measured according to the corresponding standards and ordering requirements. DC 1mA reference voltage.
3. Maintenance: In order to accumulate operating experience, the preventive test cycle is five years. The pre-test items are the leakage current under the reference voltage of DC 1mA and 0.75 times the reference voltage of DC 1mA. The measured voltage value should meet the corresponding standards and requirements.
4. Installation: The lightning arrester should be fixed on the shell or special support closer to the protected equipment, and multi-strand copper wires with a cross-section of not less than 6 square millimeters should be used to connect the upper wire terminal of the arrester to the phase wire and the lower wire terminal to the public ground. Online (grounding resistance is not more than 10 ohms).
五、User order needs
1.This product will be replaced or repaired by our company within three years from the date of shipment under the condition that the user abides by the rules of use.
2.If users have special performance requirements, they can come, write or call, and manufacture and supply according to the agreement.
3.The company is located in the Three Gorges of the Yangtze River, welcome domestic and foreign customers to visit and negotiate orders.
Telephone: 0717-4555888
Telephone: 0717-4722659
Fax: 0717-4839292
Mail box: ychykj@163.com
Address: No. 198, Chenghe Avenue, Shilipu Industrial Park, Yidu City, Hubei Province
Post Code: 443300